This unit cannot be removed or inserted with system power energized. Bussed field power must not be connected to a supply that generates or contains a source of potential in excess of 30 VDC.
Field power supplied to this device either at the field terminal or as bussed field power via the I/O carrier must be removed before removing or connecting this device.
Power must be de-energized before disconnecting any carriers or LocalBus Extender cables.
A module cover (KJ4001X1-FA1) must be fitted to any permanently unoccupied location on an I/O module carrier. (Permanently unoccupied implies no I/O module and no terminal block are intended for that location.)
This product must not be unplugged unless either the system has been de-energized or the area is known to be safe. No combination of I/O carriers and
LocalBus Extenders must exceed a length of 6.5 meters. Interconnecting cable between enclosures must be in conduit.